Loading...
Ord 2242 - Cr Conn Backflow COUNCIL BILL NO. 1983 ORDINANCE NO. 2242 AN ORDINANCE PROVIDING FOR CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION PROCEDURES; COMPLYING WITH OREGON ADMINISTRATIVE RULES 333-61-0070; AND DECLARING AN EMERGENCY. WHEREAS, the Oregon Heath Division through its administrative rules requires that the City institute a cross connection and backflow prevention program; and WHEREAS, this ordinance will serve as the enabling authority required by Oregon Administrative Rules 333-061-0070 which authorizes the discontinuance of water services to a premises for the failure to install an approved backflow device or to conduct a required annual test on a backflow device; and WHEREAS, the City will also administratively implement a local cross connection program as further specified in the Oregon Administrative Rules; and WHEREAS, it is in the public interest for the City to require the installation of backflow prevention devices and the inspections of those devices as set forth in this ordinance; NOW, THEREFORE, THE CITY OF WOODBURN ORDAINS AS FOLLOWS: Section 1. Title. This ordinance shall be known as the "City ofW oodburn Cross Connection Control and Backflow Prevention Ordinance". Section 2. Policy and Purpose. As required by the Oregon Health Division, pursuant to Oregon Administrative Rules 333-61-0070, and in order to prevent any possibility of backflow contaminating the water system, it shall be the policy of the City of Woodburn to require the installation of backflow prevention devices, and inspections of those devices, as set forth in this ordinance. The City of Woodburn shall also administratively implement a local cross connection program as further specified in the Oregon Administrative Rules and the City of Woodburn Cross Connection Implementation Manual. Section 3. Definitions. The words and phrases used in this ordinance shall have the meaning provided in Oregon Administrative Rules 333-061-0020. Section 4. Records and Reports. The City shall maintain current records of backflow assemblies installed, inspections completed, and backflow assembly test results, and shall report such data as may be required by State law. Page 1 - COUNCIL BILL NO. 1983 ORDINANCE NO. 2242 .,.-.. ,,,'_..;..-...,.._.........._~,--","-~---, T' ... Section 5. Discontinuance of Service for Violations of Policy. A. After proper notice to the customer as required by this ordinance, and until the violation has been corrected, the City shall discontinue water service to any premises under any of the following circumstances: (1) For failure to install an approved backflow prevention device; (2) For failure to conduct an annual test on the backflow device; (3) When the City has reasonable cause to believe that an existing or potential cross connection is located on the user's premises, until an appropriate backflow prevention assembly is installed or until the cause ofthe hazard is eliminated. (4) For any other violation of this ordinance. B. This section shall not in any way be construed to impair the City's ability to immediately discontinue water service in the event of imminent threat to the City's water system or other emergency situations. Section 6. Backflow Prevention: When Required. A. Backflow prevention assemblies shall be installed at the service connection to premises where an approved airgap does not exist and: (1) There is an auxiliary water supply which is, or can be, connected to the potable water plpmg; or (2) There is piping for conveying liquids other than potable water, and where that piping is under pressure and is installed in proximity to potable water piping; or (3) There is intricate plumbing which makes it impractical to ascertain whether or not cross connections exist; or (4) There is backsiphonage potential; or (5) Cross connections or potential cross connections exist. Page 2 - COUNCIL BILL NO. 1983 ORDINANCE NO. 2242 . .. ....-..... , Section 7. Approved Devices and Installation Thereof: Required Methods ofBackflow Prevention. A. New Assemblies. All backflow prevention assemblies required under this ordinance shall be of a type and model approved by the Oregon Health Division, and shall be installed in accordance with Oregon Administrative Rules 333-61-0071 Sections (1) through (4), as now existing or later amended. Suitable pressure-relief devices to prevent damage from thermal expansion shall be required in conjunction with the installation of all new backflow prevention assemblies. B. Existing Assemblies. Backflow prevention assemblies installed before the adoption of this ordinance and which were approved by the Oregon Health Division at the time they were installed, but are not on the current list of approved assemblies, shall be permitted to remain in service provided they are properly maintained, are commensurate with the degree of hazard, are tested at least annually, and perform satisfactorily. When assemblies of this type are moved, or require more than minimum maintenance or are on services that are modified, changed size or remodeled, they shall be replaced by assemblies which are on the Oregon Health Division list of approved assemblies. c. Required Backflow Prevention Methods. The method ofbackflow prevention required under this ordinance shall at a minimum be commensurate with the degree of hazard which exists, and not less than the following: (1) When the substance which could backflow could be hazardous to health, an approved air gap of at least twice the inside diameter, but not less than one inch, of the incoming supply line measured vertically above the top rim of the vessel shall be installed, or an approved reduced pressure backflow (RPBA) assembly shall be installed. (2) When the substance which could bacldlow is objectionable but does not pose an unreasonable risk to health, an approved double check valve assembly (DCV A) shall be installed. An approved double check valve assembly shall be the minimum protection for fire sprinkler systems using piping material that is not approved for potable water use and lor which does not provide for periodic flow through during each 24 hour period. (3) An approved pressure vacuum breaker assembly (PVBA) or an atmospheric vacuum breaker (A VB) shall be installed where the substance which could backflow is objectionable but does not pose an unreasonable risk to health and where there is no possibility of backpressure in the downstream piping. A shutoff valve may be installed on the line downstream of a pressure vacuum breaker but shall not be installed downstream of an atmospheric vacuum breaker. Section 8. Testine Required. A. When Required. The water user or the owner of the premises where one or more Page 3 - COUNCIL BILL NO. 1983 ORDINANCE NO. 2242 ~.-"~ - -', _,"..c,"_~__.'.,'~"o_ .',. -"""'-"-.-.r-.."-.----"'+--".........4..........~------'*'-"...-- reduced pressure assembly (RPBA), double check valve assembly (DCV A), or pressure vacuum breaker (PVBA) have been installed shall have the assemblies tested by a certified tester at least once per year. Assemblies installed at facilities which pose an extreme health risk and assemblies which repeatedly fail shall be tested on a more frequent basis as determined by the City. Backflow assemblies which have been moved or which have been installed shall be tested before use. B. Malfunctioning Assemblies. Backflow prevention assemblies found not to be functioning properly shall be promptly repaired by the owner or water user, and failure to do so may result in the denial or discontinuance of service as provided in this ordinance. c. Test Procedures and Reports. Tests performed by certified testers shall be in conformance with procedures adopted under OAR 333-061-0070 (10), as now existing or later amended. Reports on the tests shall be prepared by the certified tester and copies shall be provided to the City and to the water user or owner of the premises. Section 9. Administrative Subsidy Pro~ram. Consistent with the terms of this ordinance and subject to the City budget, the City Engineer may authorize administrative subsidies for the installation of required backflow prevention devices after a finding that such installation will protect the City water system and will benefit the public interest. Section 10. Severabilitv. The provisions of this ordinance are severable. If a portion of this ordinance is for any reason held by a court of competent jurisdiction to be invalid, such decision shall not affect the validity of the remaining portions of the ordinance. Section 11. Emer~ency Clause. This ordinance being necessary for the immediate preservation of the public peace, health and safety, an emergency is declared to exist and this ordinance shall take effect immediately upon passage by the City Council and approval by the Mayor. Approved as to form~.~ ~ ~- Z 0 - '1 '7 City Attorney Date APprOVed:~~ Ric d Jennings, Ma or Passed by the Council Submitted to the Mayor Approved by the Mayor Filed in the Office of the Recorder ATTEST: fYlCLLu ~ ~ant City Recorder City of Woodburn, Oregon August 23, 1999 August 24, 1999 August 24, 1999 August 24. 1999 Page 4 - COUNCIL BILL NO. 1983 ORDINANCE NO. 2242 .....~'" -"._, '---y-- _."-",-~."..~_._.._,,,..~,..__.._. ' ,